Silk Screen
Description
BSC
The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems,
ensuring that two buses can switch with each other.
BSC cables are hot-swappable.
NO TE
For a single UPS, the parallel cable is not needed.
Table 2-5 Indicator description
Indicator
Color
Status
Description
NORMAL
Green
Steady
on
This ECM is the active ECM.
Blinking
at 0.5
Hz
This ECM is the standby ECM and it is ready.
Off
This ECM is not ready or the software of this
ECM is being upgraded.
Blinking
at 4 Hz
The software of the ECM is being upgraded or
not configured.
ALM
Yellow
Steady
on
The ECM has a minor alarm, but it does not
need to be replaced.
Off
The ECM has no minor alarm or the software
of the ECM is being upgraded.
FAULT
Red
Steady
on
The ECM has a critical alarm.
Off
The ECM has no critical alarm or the software
of the ECM is being upgraded.
Functions
●
As a control interface for the entire system, the ECM communicates with each
module and provides a bus for communication between the dry contact card
and the system control card. The ECM ensures equalized output currents
between modules so that load power is equally shared.
●
Provides module running information for the MDU.
●
Controls the running of a single UPS and a parallel system, and reports the
UPS status information to other monitoring modules.
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
2 Overview
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
30