Item
Specifications
Input system
Three-phase four-wire + PE
Rated frequency
50 Hz/60 Hz
Frequency range
50/60 Hz ±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by
default)
Input mode
The mains input and bypass input share a power
source or use different power sources
7.7 Battery Electrical Specifications
NO TICE
The UPS supports the SmartLi. For details about the specifications, see the
SmartLi
User Manual
.
Item
Specifications
Number of batteries (lead-
acid batteries)
● 30–44 batteries. 34 batteries: battery inverter
output power is derated to 94%; 32 or 30
batteries: battery inverter output power is
derated to 80%.
● The default number of batteries is 0. Set this
parameter based on site requirements.
Cold start
In the case of a mains failure, batteries can start
the UPS to power loads.
Charger output power
(6250 W±200 W) x N. The maximum charge
power of a power module is 6250 W±200 W
(the maximum current is 10 A). N represents
the number of power modules in the rack.
Charging voltage (lead-acid
battery)
● Equalized charging voltage: 2.3–2.4 V/cell,
2.35 V/cell by default (30–42 batteries); 2.3–
2.35 V/cell, 2.35 V/cell by default (44
batteries)
● Float voltage: 2.23–2.3 V/cell, default: 2.25 V/
cell (30–44 batteries)
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
7 Technical Specifications
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
123