Indicator
Color
Status
Description
Blinking
at short
interval
s
The module is not configured, the inverter or
rectifier software is being upgraded, or the
inverter software is being upgraded (blinking
at 4 Hz, on for 0.125s and off for 0.125s).
Off
The rectifier software is being upgraded.
Alarm
indicator
Yellow Steady
on
A minor alarm is generated for the inverter or
rectifier.
Off
There is no minor alarm for the inverter or
rectifier, or the rectifier software is being
upgraded.
Fault
indicator
Red
Steady
on
A critical alarm is generated for the inverter or
rectifier.
Off
There is no critical alarm for the inverter or
rectifier, or the rectifier software is being
upgraded.
Functions
The power module consists of a power factor correction (PFC) rectifier and
inverter. It performs AC/DC or DC/DC conversion on the mains and battery inputs,
and stabilizes the bus voltage. The inverter (DC/AC) converts the inputs into sine
wave outputs.
Specifications
●
Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
●
Weight: < 21 kg
●
Rated output capacity: 30 kVA/30 kW
●
Power density: 20.64 W/inch
3
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
2 Overview
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
25