NO TE
● The input upstream circuit breakers recommended in
are for reference only.
● If multiple loads are connected, specifications for branch circuit breakers must not
exceed the recommended specifications.
● The circuit breaker selection principle is to protect loads and cables, and the cascading
principle is to realize specific protection.
3.2 Transportation, Unpacking, and Checking
Context
NO TICE
● To prevent the UPS from falling over, secure it to a pallet truck using ropes
before moving it.
● To prevent shocks or falls, move the UPS gently. After placing the UPS in the
installation position, unpack it and take care to prevent scratches. Keep the UPS
steady during unpacking.
● If the UPS installation environment is in poor condition and the UPS needs to
be stored for a long time after it is unpacked, take measures to prevent dust. It
is recommended that the UPS be wrapped with the original plastic packing.
Procedure
Step 1 Use a pallet truck to transport the UPS to the installation position.
Step 2 Check the UPS packing.
Step 3 Hold the sliding plate steady. Cut and remove the binding tapes. Put down the
sliding plate gently. See
.
Figure 3-3 Removing binding tapes
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
3 Installation
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
52