Item
Specifications
30 kVA
60 kVA
90 kVA
120 kVA
Recommende
d cross-
sectional area
(mm
2
)
L1
4 x 10
4 x 35
4 x 70
4 x 95
L2
L3
N
Bypass
input
Bypass input current (A) 45
91
136
182
Recommende
d cross-
sectional area
(mm
2
)
L1
4 x 10
4 x 25
4 x 50
4 x 70
L2
L3
N
Output
Output current (A)
45
91
136
182
Recommende
d cross-
sectional area
(mm
2
)
U
4 x 10
4 x 25
4 x 50
4 x 70
V
W
N
(When
the UPS
connect
s to a
non-
linear
load,
increase
the
cross-
section
al
area.)
Battery
input
(lead-
acid
battery)
Nominal discharge
current (A)
66
132
197
263
Maximum discharge
current (A)
79
158
236
315
Recommende
d cross-
sectional area
(mm
2
)
+
3 x 16
3 x 50
3 x 70
3 x 120
N
-
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual