CM4 Four-Point Continuous Monitor
CM4 Technical Manual
G-9
Nvi00Request accepts commands to start or stop monitor and to reset
faults. Refer to Table 1 for a list of implemented requests. Additionally,
nvo00Status conveys if the CM4/CM4-P is in or out of monitor, if a
point is enabled or disabled, and if faults or alarms are active. Refer
to Table 2 for a mapping of LonMark nomenclature to Honeywell
Analytics nomenclature.
Request
Node 0
Implementation
Nodes 1-4
Implementation
0 RQ_NORMAL
start monitor
start monitor
1 RQ_DISABLED
exit monitor
2 RQ_UPDATE_STATUS
retransmit status
retransmit status
3 RQ_SELF_TEST
4 RQ_UPDATE_ALARM
5 RQ_REPORT_MASK notify of implementation notify of implementation
6 RQ_OVERRIDE
7 RQ_ENABLE
start monitor
8 RQ_RMV_OVERRIDE
9 RQ_CLEAR_STATUS
10 RQ_CLEAR_ALARM clear all alarms, faults clear all alarms, faults
Table G-1: Implemented Requests
Nvo00FaultS reports the existence of any fault. The state byte of this
two-byte structure will contain a FALSE (0) if no fault is active or a
TRUE (1) if a maintenance or instrument fault exists. The value byte
will contain the fault number.
Nvo00FaultID reports the presence of faults in a simpler format for
consumption by true peer nodes. This contains ST_OFF, or 0, if no
fault exists, ST_LOW, or 1, if a maintenance (minor) fault exists, and
ST_MED, or 2, if an instrument (serious) fault exists.
Status Field
Node 0 interpretation
Nodes 1-4 interpretation
object_id (16 bits)
0
1-4
invalid_id
object_id >4
object_id >4
invalid_request unimplemented request made unimplemented request made
disabled
out of monitor disabled by configuration or
PntLockon
out_of_limits
open_circuit
out_of_service
mechanical_fault
instrument (serious) fault
instrument (serious) fault
feedback_failure
over_range
alarm is level 2 any pt
alarm is level 2 this pt
under_range
electrical_fault
maintenance (minor) fault
maintenance (minor) fault
unable_to_measure
disabled by fault
comm_failure
fail_self_test
host is dead
host is dead
self_test_in_progress
locked_out
manual_control
in_alarm
alarm any level, any pt
alarm any level this pt
in_override
report_mask
mere capability report
mere capability report
Table G-2: LonMark
®
and Honeywell Analytics Nomenclature
Nvo0xAlmL (five variables) report the alarm state of the CM4. The
four variables nvo01AlmL through nvo04AlmL convey the alarm level
of the four points. ST_OFF is transmitted when no alarm exists, ST_
LOW is transmitted when a level 1 alarm is present, and ST_MED is
transmitted when a level 2 alarm is active. The general alarm variable
珠海司福斯特科技有限公司
www.safedtech.com