CM4 Four-Point Continuous Monitor
CM4 Technical Manual
6-9
5/15/05 10:06 CM4-851-0000
SYSTEM CONFIGURATION PRINTOUT
ABC MANUFACTURING CO., CHICAGO, IL.
Chemcassette:
Hydrides
NAME
ABBREVIATION
ARSINE
AsH
3
PHOSPHINE
PH
3
SILANE
SiH
4
DIBORANE
B
2
H
6
TERTIARYBUTYLARSINE
TBA
HYDROGEN SULFIDE
H
2
S
DRY ARSINE
AsH
3
/D
HYDROGEN SELENIDE
H
2
Se
NAME
GAS
K-FACTOR
ALARM 1
ALARM 2
20 mA FS
ENABLE
PT1-CM4-851-0006
AsH
3
1.000
50ppb
100ppb
500ppb
YES
PT2-CM4-851-0006
AsH
3
1.000
50ppb
100ppb
500ppb
YES
PT3-CM4-851-0006
AsH
3
1.000
50ppb
100ppb
500ppb
YES
PT4-CM4-851-0006
AsH
3
1.000
50ppb
100ppb
500ppb
YES
RELAY STATE .............................................................................LATCHING .................................................................... DE-ENERGIZED
2 mA FAULT INDICATION .....................................................DISABLED
PUMP LIMITS ............................................................................500, 400
DISPLAY UPDATE TIME ..........................................................4 SECONDS
TWA PRINT TIMES ...................................................................00:00, 08:00, 16:00
PRINTER PORT..........................................................................9600 BAUD
HAND SHAKE ...........................................................................DISABLED
PRINTOUT SELECTED ............................................................COMPRESSED
IDLE TIMEOUT ..........................................................................45 MINUTES
DUTY CYCLE 000 SECONDS ................................................POINTS LINKED TO MONITOR RELAY (1, 2, 3, 4)
SERVICE HISTORY ............................................................................................................................................................
INT. FILTER LIFE ......................................................................0 DAYS
EXT. FILTER LIFE .....................................................................0 DAYS
Chemcassette REMAINING..................................................0 DAYS
LAST OPTICS VERIFICATION: ...............................................05/15/05 10:06
LAST FLOW BALANCE: ..........................................................05/15/05 10:06
COM PROTOCOL VERSION 1 ...............................................ADDRESS OO1. 9600 BAUD
KEYBOARD LOCK ....................................................................DISABLED
MENU PASSWORD ..................................................................DISABLED
DATE FORMAT ..........................................................................MM/DD/YY
TAPE ADVANCE SENSOR ......................................................128P .............................................................................. STATUS 04CF 68A7 4846
END OF SYSTEM CONFIGURATION PRINTOUT * * * * * * * * * * * * * * * * * * *
Figure 6-6: Typical Configuration Printout
珠海司福斯特科技有限公司