Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
9-13
7.
Select the type of device by pressing the up or down arrow key. Refer to Table 9-4 under the column heading
“Type Selection” for a list of choices.
Table 9-4 Point Programming for 6815
Type
Selection
Function
Latching Option
Comments
UNUSED
Select for SLC points that are unused.
DETECTOR
PHOTO
Spot photoelectric detectors.
ION
Spot ionization detector.
HEAT
Spot heat detector.
PHOTO DUCT
Duct photoelectric detector.
ACCLIMATE
Acclimate photoelectric detector.
HEAT HT
High temperature heat detector.
PHOTO-HEAT
Photoelectric detector with heat sensor.
BEAM
Beam smoke detector.
SUP DET
PHOTO
Latching
Non Latching
Use this option when you want a detector to indicate a supervisory
alarm.
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO SMOKE
DETECTOR
CO ALRM /
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
FIRE SUPR
Latching
Non Latching
Detectors programmed as Supervisory can be latching or non-
latching.
W-DETECTOR
Photo
Wireless photoelectric detector
Photo-Heat
Wireless heat detector
Heat
W-SUP-DET
Same as W-
Detector
Latching
Non Latching
SWITCH
MANUAL PULL
Use this switch type for manual pull stations. This input is always
latched. The switch can clear only when an alarm is reset. This
switch type has the highest fire priority; it overrides any other type of
fire alarm.
WATERFLOW
Latching
Use this switch type for monitoring water flow in a sprinkler system.
Switch closure will cause a sprinkler alarm. Water flow switches can
be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a
water flow switch. The delay allows for normal, brief changes in
sprinkler system water pressure. The water flow alarm will not
activate unless the switch is active for the programmed delay time.
If a delay is used, the system begins counting down when the switch
closes. If the switch opens (restores) before the timer expires, a
water flow alarm is not generated. If the water flow switch remains
closed after the timer expires, a water flow alarm will be generated.
Non Latching