background image

TSFC 12-2 User Manual 

Vighnaharta technologies Pvt. Ltd.                                                     Page 

1

 of 

26

 

 

 

 

TSFC 12-2 

USER MANUAL  

 

 
 
 
 

 

 

Mfg. By: 
Vighnaharta Technologies Pvt. Ltd. 
 
2nd Floor,Karanjkar Estate,S.N.11/11,Nanded Gaon,Pune-411041 
Contact no.: +919011033259 (Landline)    Sales: +919011033260 
Email: [email protected]  |  Website: 

http://www.vighnaharta.in

 

 

 

 

 

Vighnaharta Technologies Pvt. Ltd. 

2nd Floor,Karanjkar Estate, 
S.N.11/11,Nanded Gaon, 
Pune-411041 
Tel no.: +919011033259,  Sales: +919011033260 
Email: [email protected]  |  Website: http://www.vighnaharta.in 

Prepared By: SBK 
Approved By: NK                                                   

Doc No.:  TSFC 12-2_UM_4_0 
 Rev.No.:  4_0 
 Eff.Date.: 20-12-2018 

Summary of Contents for TSFC 12-2

Page 1: ...1 Contact no 919011033259 Landline Sales 919011033260 Email sales vighnaharta in Website http www vighnaharta in Vighnaharta Technologies Pvt Ltd 2nd Floor Karanjkar Estate S N 11 11 Nanded Gaon Pune 411041 Tel no 919011033259 Sales 919011033260 Email sales vighnaharta in Website http www vighnaharta in Prepared By SBK Approved By NK Doc No TSFC 12 2_UM_4_0 Rev No 4_0 Eff Date 20 12 2018 ...

Page 2: ...sity levels are not created by developing fire at the location of detectors the detectors will not go into alarm Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time for this reason the rate of rise feature of each d...

Page 3: ...r operation However the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment conditions specified Verify that wire sizes are adequate for all initiating and indicating device loops Remove all electronic assemblie...

Page 4: ...hnologies Pvt Ltd Page 4 of 26 RECORD OF REVISION Rev Date Prepared By Reviewed By Approve d By Description Remarks on Release 3_0 20 08 18 SBK NMK NMK Initial draft 4_0 20 12 18 MDC NMK NMK NAC Silence Time Menu removed from Menu options ...

Page 5: ...arta technologies Pvt Ltd Page 5 of 26 Abbreviations TSFC 12 2 TrueSafe Fire Cloud with 2 Input Zones IDC Initiating Device Circuit NAC Notification Appliance Circuit ACK Acknowledge MCP Manual Call Point PFC Potential Free Contact ...

Page 6: ...el Wiring 13 2 3 1 Field Wiring Diagram 14 2 3 2 Initiating Device Circuit IDC 14 2 3 3 Output Circuits 15 2 3 4 NAC 15 2 3 5 Fixed Output PFC Optional 15 2 3 6 Resettable 12VDC output 16 2 4 Maintenance 16 2 4 1 Walktest 16 2 4 2 Servicing 16 2 4 3 Periodic inspection and test of system 17 2 4 4 Pre Check list for call 17 2 5 Do s and Don ts 18 2 5 1 Do s 18 2 5 2 Don ts 18 3 System Programming 2...

Page 7: ...TSFC 12 2 User Manual Vighnaharta Technologies Pvt Ltd Page 7 of 26 4 1 2 Fault Condition 25 4 2 Wi Fi 26 ...

Page 8: ...can continuously monitor for trouble and fire condition as well as send their status on Fire Cloud A user friendly Android iPhone Mobile application is available for Fire and Fault notification from the TSFC panel and can be downloaded from Google PlayStore or Apple Store 1 2 System Features Operated on 12 V 1 2 Ah DC power supply with built in charger Battery low voltage 11 V DC and battery cut a...

Page 9: ... LED indications SYSTEM ON MAINS FAIL BATTERY FAULT NAC FAULT Siren SILENCE WiFi Zone Fault Walk Test Mode Zone Bypass Fire WALK TEST 16 x 2 LCD Display Indication Zone fire status fault status configuration menus Etc Buzzer Indication Fire Fault Walk Test Fire Key press acknowledge Output NAC Siren Output Voltage 12 VDC Current 500 mA Optional PFC Relay outputs 3 Dimensions 237 x 217 x 42 L x H x...

Page 10: ... RESET OR Num key 5 Yes Reset the system OR Enter numeric values 5 during configuration OR Num Key 0 Yes Scroll Right OR Enter numeric values 0 during configuration 1 4 2LED Indications There are different LED indications given on front panel of TSFC panel to user to alert from different events occurred Name of events along with colour of corresponding LED with description are as follows No Indica...

Page 11: ...etting Change user password 1 4 4Buzzer Indications A buzzer provides separate and distinct sounds for Fire Faults and Walk Test Fire Fire Continuous Buzzer ON Fault 1 sec ON and 5 sec OFF Walk Test Fire 1 sec ON and 1 sec OFF 1 4 5EOL Resistor 820 ohm 1 W Resistor is connected in parallel with each input zone for zone open short fire sensing purpose Hence 2 resistors are required for TSFC 12 2 mo...

Page 12: ...ystem works at 0 C to 50 C and at a relative humidity of 90 2 RH However the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity 2 2 Mounting Details Backside of the panel Place the panel in its mounting position and fix the panel to the wall using the slots of the two screws Ensure the enclosure and the i...

Page 13: ... The panel and associated equipment may be damaged by removing and or inserting cards modules or inter connecting while this unit is energized Primary Power source AC and Earth Ground Connection AC Power connections are made inside the control panel cabinet A separate Earth Ground connection must be made to ensure the proper panel operation and lightening and transient protection Standby Power Sou...

Page 14: ...wing diagram shows connector s placement on Interface board 2 3 2Initiating Device Circuit IDC No of Initiating circuit 2 Zone Type Class B Wire Size 1 sq mm FRLS cable Operating Voltage 12 VDC nominal max Connector J2 Total No of Devices Up to 20 smoke detectors per zone Monitoring Device 820 Ohm 1 W EOL ...

Page 15: ...on Appliance Circuit NAC Potential Free Contact Relay Outputs PFC 2 3 4NAC No of NAC 1 circuits Type Class B Output Voltage 12V Current 500mA max Terminals J2 Wire Size 1 sq mm FRLS cable 2 3 5Fixed Output PFC Optional Three PFC outputs 1 Fire1 status output 2 Fire2 status output 3 Fault status output ...

Page 16: ...icular zone The sensor will reset automatically and will come back to normal condition In this way multiple sensors in a single loop can be tested Note Repeat Walk test after every 3 months 2 4 2Servicing Following are the servicing check list of TSFC panel Maintenance servicing are required at least twice a year for each panel Sr No Check point or maintenance point OK Not OK Remark 1 Clean each s...

Page 17: ...into the log book Quarterly Test Perform Walk Test Supervisory Test to check the healthy condition of all zones After every 3 4 months Walk test must be carried out Annual Test Additionally test all detectors check points and check for correct operation Every 2 3 Years Clean smoke detectors to ensure correct operation and freedom from false alarms Special equipment is required for cleaning smoke d...

Page 18: ...de both periodic preventative maintenance activities and making the required repairs revealed by the inspection or testing of the system components like DSPA siren 4 DO train your people Certain people must receive varying degrees of training depending upon their role Some must understand how to operate the system so they can interact with the system when something happens Others must simply be re...

Page 19: ...r It s important to put in place and enforce procedures and policies that will minimize the chance for this sort of error The single biggest contributor to the prevention of accidental discharges is training the personnel who work in and around these spaces 4 DON T allow unqualified personnel to service your fire system Facilities Managers must ensure those who are performing these tasks are train...

Page 20: ...er cannot enter in MENU function Factory default panel do not have any password If user enables Auto Key Lock function only that time panel will ask password Factory default password is 1111 To enter into Programming mode do following steps 1 Press MENU key it will ask for password If Auto Key Lock function is enabled 2 Enter FOUR digit numeric passwords 3 After entering the password user can acce...

Page 21: ...WT means Walk Test 3 Disabled This mode is used to disable the zone The system does not scan the input signal from smoke detectors heat detectors etc 3 1 2Zone 2 After entering in the Zone 2 menu LCD displays as shown below Use LEFT and RIGHT keys to view sub menu of ZONE 2 configuration After changing the mode press ENTER key to save the changes Each zone can be configured for any one of the THRE...

Page 22: ...put After changing the mode press ENTER key to save the changes By default it is enabled NAC silence time set as a 10min and is not user editable 3 1 5Auto Key Lock This function is used to LOCK panel keypad automatically after completion of Auto Key Lock timer If this menu is set as a DISABLE panel keypad will not get locked By default it is set as a DISABLE Auto key lock timer is set as 3 minute...

Page 23: ... using internet and Mobile application User can monitor Fire panel status on an Android or iOS app If user enables this mode and connects the panel to Wi Fi all panel notifications are received to user on the mobile application A RESET switch is also available in front panel of Fire panel It is use to reset the Configuration of Wi Fi setting Use LEFT and RIGHT keys to ENABLE DISABLE WIFI function ...

Page 24: ...lains the system behaviour under different conditions The System continuously monitors for fire and system faults in all modes of operation When system is powered ON System ON LED is continuously ON LCD displays show below screen If panel mains is not available panel will be shifted to battery mode as well as MAINS FAIL led will also glow for notification to user TrueSafe SYSTEM OK ...

Page 25: ...set action is carried out by user OR till silence time is not completed The fixed TWO Fire output of the relay gets activated Fire alarms are latched and are not allowed to clear automatically Timer for NAC Silence starts If any zone is in Walk test mode it exits the Walk test mode FIRE notification send to the FIRE CLOUD application through Wi Fi if Wi Fi is enabled 4 1 2Fault Condition If system...

Page 26: ...red Fault notification send to the FIRE CLOUD application through Wi Fi 4 2 Wi Fi Wi Fi cloud connectivity is a unique feature built in in TSFC 12 2 Fire Alarm Panel The user can enable or disable this feature from the panel keypad The Wi Fi feature can be used with Vighnaharta s TrueSafe Cloud Mobile application on Android or iPhone Refer the Vighnaharta TrueSafe Mobile Application user guide for...

Reviews: