LS10144-001SK-E
Programming
9-22
9.6.1.5 Phone Line Gains
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 5 for Phone Line Gains
6.
The available options: *default
•
Dialing Gain:
•
Low = 9 DB Attenuation
•
Normal = 6 DB Attenuation
•
*High = 3 DB Attenuation
•
Reporting Gain:
•
*Low = 9 DB Attenuation
•
Normal = 6 DB Attenuation
•
High = 3 DB Attenuation
9.6.2
Time Options
Through this programming option you can set the water flow delay time, alarm verification time, AC report
delay, AC-Frequency, Auto-Resound, and Clock Format.
9.6.2.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 4 for Time Options.
A screen similar to the one shown in Figure 9-10 will display.
Figure 9-10 Water Flow Delay Programming Screen
5.
Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press ENTER.
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)