LS10144-001SK-E
Control Panel Installation
4-26
5.
Press the right arrow to skip over the Enter Module ID and Enter Module name options. A screen similar to
the one shown in Figure 4-34 will display.
Figure 4-34 Selecting Printer and Output Port Options
6.
Select options for the printer as needed for your installation. Most printers are parallel.
7.
If you are using a serial printer, use the next screen to select serial port options as required for your printer.
Refer to your printer manual if you need more
information.
4.11 5880 LED I/O Module
The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with
most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller.
The 5880 also has eight inputs for monitoring dry contacts. When used with the 6820EVS the 5880 inputs can be
programmed to replicate the eight EVS buttons located on the front of the voice control module. (See section 9.5
for programming options). Up to 8 5880s can be added to the 6820/EVS system.
The following sub-sections describe hardware installation. Refer to Section 9 for programming information.
4.11.1
5880 Board Layout
Figure 4-35 shows the locations of screw terminals for connection to the panel and contact monitor wiring; pin
Option
Choices
Baud Rate:
75 - 19200
Data Bits:
5 - 8
Stop Bits:
.5, 1, 2
Parity:
None, Even, Odd
Defaulted to no
Select “Yes” for event logging
Select type of printer
Parallel or Serial