Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
12-1
Section 12
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control
panel for SIA and Contact ID formats.
12.1 Receivers Compatible with the Control Panel
Table 12-1 shows receivers compatible with the control panel.
Table 12-1: Receivers Compatible with the Control Panel
Manufacturer
Model
Format
Honeywell
Model 9800
SIA and Contact ID
Model 9000 (SIA formats)
SIA
Honeywell Security
AlarmNet 7810-ir
IP and Cellular Receiver,
Contact ID only
Ademco
MX8000
SIA and Contact ID
Ademco
Model 685 (Contact ID )
Contact ID
Sur-Gard
SG-MLR2-DG (V. 1.64 or higher)
SIA and Contact ID
Osborne Hoffman
Quickalert
SIA and Contact ID
Table 12-2: Reporting Formats Table
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
System Events
Note:
System Events are reported when either “Report by Point” or
Report by Zone is selected
AC power low trouble
AT
0
ATNN000000
1
301
00
000
AC power low trouble restore
AR
0
ARNN000000
3
301
00
000
Auto dialer test communications
trouble line 1
YC
1
YCNN000001
1
350
Receiver # 001
Auto dialer test communications
trouble line 1 restore
YK
1
YKNN000001
3
350
Receiver # 001
Auto dialer test communications
trouble line 2
YC
2
YCNN000002
1
350
Receiver # 002
Auto dialer test communications
trouble line 2 restore
YK
2
YKNN000002
3
350
Receiver # 002
Automatic test normal
RP
0
RPNN000000
1
602
00
000