LS10144-001SK-E
Control Panel Installation
4-34
2.
Configure the circuit through programming (see Section 9.5).
Figure 4-45 Class B Input Switches
4.15.2
Class A Inputs
You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the
Flexput circuits of the control panel.
To install a Class A switch:
1.
Wire the Class A switch as shown in Figure 4-46.
2.
Configure the circuit through programming (see Section 9.5).
Figure 4-46 Class A initiating Switches
Supervised
Power Limited
UL Listed
EOL 4.7 k
Supervised
Power Limited
Maximum Impedance
per circuit is 50W