LS10144-001SK-E
Programming
9-12
9.5.2
Point Programming For 6815 Module
To program for points on an 6815 module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 Quick Reference Table for
available choices. Then press ENTER.
5.
Select S for sensor or M for module. (SK Only)
6.
Enter the number of the point you wish to edit, then press ENTER.
SWITCH
(cont.)
INTERLOCK
Interlock release switch input.
STATUS POINT
EVS INPUT
Latching
User also has EVS Event Number 1-8 option for EVS INPUT.
Only available when an EVS-VCM is installed in the system.
Non Latching
EVS TAMPER
Latching
Non Latching
EVS SUPER-
VISORY
Latching
Non Latching
CO DETECT SW
CO Detector Switch
CO
SUPERVISORY
DETECT SW
CO Supervisory Detector Switch
NOTIF
OUTPUT PT
Select Group
Output point, a general use notification type. Use for driving
standard notification appliances.
AUX CONST
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
AUX RESET
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
RELAY
OUTPUT PT
Select Group
Output point, a general use relay type. Use for applications requiring
a relay, such as fan shutdown, elevator recall, and so on.
AUX RESET
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
SLC LED
LED NUMBER
01-80
For use with SD devices only. 80 sub addresses on LED.
LED FUNCTION
Unused
NOTIF
Notification can have group number.
Table 9-3: Programming Options for 5815XL Modules
Type
Selection
Function
Latching Option
Comments