LS10144-001SK-E
SK, SD and SWIFT™ Wireless SLC Device Installation
7-8
2.
Set the address for each device as described in Section 7.9.
Figure 7-6 Heat or Smoke Detector Connection to the FACP
7.9
Addressing SD SLC Devices
This section tells how to address detectors and modules. See Table 7-2 for a list of detectors that are easily
addressed at the FACP. The Installer Code is required to perform this task.
To address:
1.
Connect a detector base temporarily to the programming terminals as shown in Figure 7-7. (You can use the
same base for each detector.)
Figure 7-7: Temporary Connection of Detector Base to Panel for Addressing
2.
Enter the Installer code. The panel will automatically go to the main menu.
3.
Select 2 for Point Functions.
4.
Select 3 for Set SLC Device Address.
5.
Select “Yes” by pressing the up arrow, then press ENTER. (The panel will go into trouble at this point. You
can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel re-boots
when you finish programming.)