LS10144-001SK-E
Programming
9-18
8.
Use the up or down arrows to modify and remaining options and use ENTER to move to the next field.
9.
Edit module name. See Section 9.2.1.2. or, Press the right arrow to skip module name edit.
10. Repeat Steps 1 through 9 for all points.
9.6
System Options
This section of the manual explains how to customize software options that affect general operation of the
system. This includes such items as: Communication Options, Time Options, Miscellaneous Options, Daylight
Saving Options, Edit Banner, and SLC Family. Refer to each individual subsection for complete instructions.
9.6.1
Communication Options
9.6.1.1 Auto Test Time
To access the Auto Test Time screen:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
Table 9-6: Point Programming Options for EVS-VCM and EVS-RVM
Choices
Type Selections
Function Selections
for each Type
Comments
EVS-VCM/EVS-RVM
UNUSED
SWITCH
MANUAL PULL
Refer to comments column of
Table 9-5 for description of these
options. Latch or Non-latching feature
only appears for waterflow,
supervisory, tamper, zone aux1, zone
aux2, system aux1, and system aux2.
WATERFLOW
FIRE SUPERVISORY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
VOICE AUX STATUS 1-2
VOICE AUX EVS 1-4
Background Music
EVS INPUT
User also has EVS Event Number 1-8
option for EVS INPUT.
Only available when an EVS-VCM is
installed in the system to the EVS-
VCM / EVS-RVM choice part.
EVS TAMPER
EVS SUPERVISORY