LS10144-001SK-E
Reporting
12-14
4.
When reporting by point is enabled, the communicator uses a “pi” event to supersedes the actual point event
to report the module the point is linked to.
5.
Panel ID is not sent in the SIA event parameters.
For Example see Table 12-3:
12.3 SIA – Panel Communicator:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE Event code (2 characters)
PP Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
Table 12-3: SIA- Panels - PI Modifier Reporting Examples
Event
Re
po
rt
Zon
e
/ Point
Panel
ID
Mo
dule
Z
one ZZZ
Z
Poi
n
t
ZZZZ
F
ields Sent
SI
A Ev
ent
Da
ta
Fire Alarm-Zone
Zone
n/a
n/a97
15
n/a
EE-ZZ
FA15
Fire Alarm-Zone
Zone
n/a
n/a
05
n/a
EE-Z
FA5
Fire Alarm-Point
Point
n/a
01
n/a
123
EE-ZZ /EE-
ZZZ
pi01/FA123
Fire Alarm-Point
Point
n/a
33
n/a
203
EE-ZZ /EE-
ZZZ
pi11/FA203
Expander Trouble
n/a
n/a
11
n/a
n/a
EE-ZZ
ET11
Auto Test
n/a
n/a
n/a
n/a
n/a
EE-Z
RP0
Battery Trouble-Panel 32
n/a
n/a
98
n/a
n/a
EE-ZZ
YT98
Battery Trouble-Expander
18
n/a
n/a
18
n/a
n/a
EE-ZZ
YT18
SLC Loop Shorted
n/a
n/a
44
n/a
n/a
EE-ZZ
ET44
Program Begin Panel
ID=32
n/a
n/a
n/a
n/a
n/a
EE-Z
LB0
Program Begin Panel ID=
22
n/a
n/a
n/a
n/a
n/a
EE-Z
LB0
AC Power Loss - Panel 22
n/a
n/a
98
n/a
n/a
EE-Z
AT0
Fire Trouble
Point
n/a
97
n/a
200
EE-ZZ /EE-
ZZZ
pi97/FT200
Fire Trouble
Zone
n/a
97
01
n/a
EE-Z
FT1
Fire Trouble-Nac
Point
n/a
98
n/a
Nac
Circuit 7
EE-ZZ /EE-
Z
pi98/FT7
Z=Pt. #
Fire Trouble-Nac
Zone
n/a
98
n/a
Nac
Circuit 7
EE-ZZZ
FT400
ZZZ=OPG#