background image

 

30308005                                                                                                                                                                    Issue 1.07

 

                                       

 

Features 

  With 

“sandwich” structure, it is easy to be installed 

between DB-01 base and a detector. 

  Three working modes settable  (Mode I, II, III, and 

the latter two available with pre-alarm state). 

  16 tones of sound and bright flashing light. 

  Electronically  addressed.  The  address  and  tones 

can be modified in field. 

  Tone 14 and 16 are certified by EN54-3. 

Description 

DI-9406  Addressable  Flashing  Beacon  Base  is 
installed  in  field  to  warn  people  for  evacuation  with 
audible and visual alarm in case of a confirmed fire. 
The  flashing  beacon base  can  communicate  with  fire 
alarm  control  panel  (FACP)  through  a  built-in 
microprocessor.  On  receiving  a  start  command  from 
the FACP, the microprocessor will control the buzzer to 
generate  the  pre-set  fire  alarm  sound  and  light  the 
bright LED.

 

Wiring and Connection 

Terminals  of  the  flashing  beacon  base  are  shown  in 
Fig. 1. 

15

2.

4

10

3

59

43

A

B

 

Fig. 1   

Z1(1), Z2(3): Signal loop of FACP, polarity-insensitive.   

Recommended Wiring 

1.0mm

2

 or above fire cable, subject to local codes. 

Installation 

Warning:  Before  installing  the  flashing  beacon 
base,  disconnect  power  from  the  loop  and  verify 
that  all  the  bases  are  securely  fixed  and  that  the 
wiring is correct on each base. 

1  Before  installation,  make  sure  the  enclosure  is 

free  from  scratch  or  distortion,  and  labels  are 
complete. 

2  Installation schematic of the flashing beacon base 

is shown in Fig. 2. 

3  Secure  the  detector  base  (Fig.  4)  with  2  tapping 

screws,  and  wire  them  properly.  Align  the 
orientation mark B on the flashing beacon base to 
mark  C  of  detector  base,  and  rotate  the  flashing 
beacon base clockwise to D. Refer to Fig. 3 and 4. 

4  If  the  flashing  beacon  base  comes  with  a  cover, 

align the orientation mark on the cover to mark A 
of the flashing beacon base (Fig.1), and rotate the 
cover clockwise to B. If it's used as detector base, 
remove the cover and install the detector on it with 
the same method. 

Electric Box

Flashing Beacon Base

Base

Cover or Detector

 

Fig. 2   

 

 

 

 

 

 

             

  Fig. 3                              Fig. 4   

Application 

The flashing beacon base can be used as the base of 
intelligent  heat  and  smoke  detectors  to  combine 
detection  and  alarm  in  a  single  device.  It  can  be 
connected  to  the  loop  of  FACP  without  additional 
power supply. 

Working Mode Setup and Tone Selection

 

The  flashing beacon  base  has three  working modes. 
The factory default is tone 14, mode I.   
The flashing beacon base has  16 tones, the setup of 
which also decides the setup of working modes. 

  If  the  flashing  beacon  base  is  set  with  one  of  the 

tones from No. 1 to 16, it works in Mode I. 

  If it is set with one of the tones from No. 17 to 32, it 

works in Mode II. 

  If it is set with one of the tones from No. 33 to 48, it 

works in Mode III. 

  Tone 1~16, 17~32  and tone 33~48 are completely 

the  same  by  one-to-one  correspondence,  with  the 
only  difference  that  they  work  in  different  modes. 
Please refer to the table of tones. 

Working Modes: 

 

 

 

Mode 

Address 

Type of fire alarm 

I

 

Single address, 
occupying one 
loop point 

Note: Detector 
& beacon base 
must have 
different 
addresses.

 

Standalone. The beacon 
base gives alarm signal 
when started. 

II

 

Dual addresses, 
sharing high 
address with 
detector 

The beacon base gives 
pre-alarm signal when 
starting the higher address 
and alarm signal when 
starting the lower address. 

III 

Occupying dual 
addresses 
individually 

The beacon base gives 
pre-alarm signal when 
starting the lower address 
and alarm signal when 
starting the higer address. 

 

DI-9406

 

Addressable Flashing Beacon Base

 

B

C

D

2831-CPR-F0036 
    GST-0003-01 

              13 

548e/07 

Reviews: