LS10144-001SK-E
Before You Begin Installation
3-2
3.4
Electrical Specifications
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal Label
Description
Rating
Earth
Ground
Faults
Voltage
Current
L
AC input (hot)
120 VAC, 60 Hz
3.3 A
N/A
Earth ground
N/A
N/A
N/A
N
AC input (neutral)
120 VAC, 60 Hz
3.3 A
N/A
–
NAC 6
Flexput™ Circuits
24 VDC
3.0A notification and auxiliary
power circuits
0
+
100 mA for initiation circuits
–
NAC 5
Flexput™ Circuits
24 VDC
3.0A notification and auxiliary
power circuits
0
+
100 mA for initiation circuits
–
NAC 4
NAC Circuits
24 VDC
3.0A notification and auxiliary
power circuits
0
+
–
NAC 3
NAC Circuits
24 VDC
3.0A notification and auxiliary
power circuits
0
+
–
NAC 2
NAC Circuits
24 VDC
3.0A notification and auxiliary
power circuits
0
+
–
NAC 1
NAC Circuits
24 VDC
3.0A notification and auxiliary
power circuits
0
+
B
SBUS OUT
SBUS communication
5 VDC
100 mA
0
A
+
SBUS power
24 VDC
1.0 A
-
B
SBUS IN
Used for Class A installations
0
A
+
-
B
EXT. Comm
Cellular Connection
input
0
A
+
55 mA, 100 mA
-
N.C.
RELAY 1
General Purpose Relay 1
24 VDC
2.5 A, resistive
N/A
C
N.O.
N.C.
RELAY 2
General Purpose Relay 2
24 VDC
2.5 A, resistive
N/A
C
N.O.
N.C.
TROUBLE
Trouble Relay
24 VDC
2.5 A, resistive
N/A
C
N.O.