Control Panel Installation
4-38
4.16 Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification appliances for Class A and Class
B configurations.
4.16.1
Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class B Notification appliance circuit:
1.
Wire Class B Notification appliances as shown in Figure 4-51.
2.
Configure the circuit through programming (see Section 9.5).
Figure 4-51 Class B Notification Appliance Circuit Wiring
Maximum voltage drop is 3V per Class B notification. See Table 4-4.
4.16.2
Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A in the back of this manual.
To install a Class A notification appliance circuit:
Table 4-4: Maximum Impedance Class B
Current
Maximum Impedance
1.0A
3
1.5A
2
2.0A
1.5
2.5A
1.2
3.0A
1.0
Alarm Polarity Shown.
4.7 k
EOL
supervised
power limited
notification wiring
Max. Impedance: 1.5
Regulated 24 VDC Full Wave Rectified
27.4 VDC, 3A per Circuit, 6A max Combined