LS10144-001SK-E
Programming
9-10
9.5
Point
You may need to change characteristics of individual input points (detectors and switches) even after using
JumpStart
®
. This section explains how to change options for: type of point, latching/non-latching, silenceable/
non-silenceable, zone assignment (input points), detector accessory base options, group assignment (output
points), and point name.
9.5.1
Point Programming For 5815XL Module
To program points on 5815XL Module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
4.
Press the Up or Down arrows to select the desired module. Refer to Section 8.5 Quick Reference Table for
available choices. Press ENTER.
5.
Enter the number of the point you wish to edit, then press ENTER.
6.
Select the type of device by pressing the up or down arrow key. Refer to Table 9-3 under the column heading
“Type Selection” for a list of choices.
Table 9-3: Programming Options for 5815XL Modules
Type
Selection
Function
Latching Option
Comments
UNUSED
Select for SLC points that are unused.
DETECTOR
PHOTO
Spot photoelectric detectors.
ION
Spot ionization detector.
HEAT
Spot heat detector.
PHOTO DUCT
Duct photoelectric detector.
2-WIRE SMOKE
2-wire smoke detector.
SUP DET
PHOTO
Latching
Non Latching
Use this option when you want a detector to indicate a supervisory
alarm.
ION
HEAT
PHOTO DUCT