Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
9-1
Section 9
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using HFSS Honeywell Fire Software Suite.
9.1
UL 864 / UL 2572 Programming Requirements
Important!
Before any customized programming is done, JumpStart
®
should be run first. After JumpStart
®
is
run, thoroughly test the system. The reason the system should be tested after JumpStart
®
is because
JumpStart
®
automatically programs the system, searching for and configuring all SLC and SBUS
devices it finds. JumpStart allows you to confirm the integrity of the installation prior to performing
any custom programming. After determining that the hardware is properly installed, custom
programming can be performed.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES:
This product incorporates field programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 and UL 2572,
certain programming features or options must be limited to specific values or not used at all as indicated below.
Programming
Option
Menu Item
Permitted
in
UL 864
(Y/N)
Permitted
in
UL 2572
(Y/N)
Possible
Settings
Settings
Permitted in
UL 864
Settings
Permitted in
UL 2572
Time Options
Auto-resound
Yes
Yes
4 hrs, 24hrs
4 hours if using
SWIFT devices
4 hours if using
SWIFT devices
Time Options
Low AC Report Delay Yes
Yes
0–30 hours
1–3
1–3
Display Oldest Event Y (Enabled)
Yes
Yes
Yes & No
Yes
Yes
N (Disabled)
No
No
Yes & No
No
No
Initial Delay
0-28
Yes
Yes
0-28
3
3
Inter Message Delay
4-32
No
No
4-32
4-32
4-28
Alarm Verification
Alarm Verification
Yes
Yes
60-250
(confirmation
period)
60
60
Auto Reset EVS MIC
Triggered Event
Auto Reset EVS MIC
Triggered Event
Yes
Yes
Never
Timer Event
Disabled
Never
Timer Event
Disabled
Never
Timer Event
Disabled
EVS Input
EVS Input
Yes
Yes
Latching
Non-Latching
Latching
Latching
Event Priority
CO Alarm
No
No
Yes & No
No
No