11.8 Recording Custom Messages
The EVS-Series controls come with 15 recordable message slots. Message 1-15 can be recorded from the
microphone, Aux Input or by using the HFSS Honeywell Fire Software Suite message management utility. All
messages can be a maximum of one minute.
When in the record mode the EVS-VCM switches will function as follows:
While in the Local Record mode, select keys 1-15 will be used to reference message slots 1-15. The associated
green Select Key will indicate that a message is currently programmed in the corresponding slot. When there is
no message recorded (or the message is erased), the associated green Select Key LED will be off. While
recording a particular message, the red Select Key will turn on until recording is completed. The Select Key 1-15
will be used to playback a recorded message or to select a message slot to record to or erase.
When in the Local Record mode, the EVS-VCM LEDs will function as follows:
Table 11-1: LED Functions During Programming
Switch LED
Active LED Status
Meaning
Select Key 1-15 Green LED
On
Message is currently programmed in this slot
Select Key 1-15 Red LED
On
Message recording is in progress
Select Key 1-15 Green/Red LED
Off/Off
Message slot is empty
Message
Message
Key 1
Key 3
Message
Key 8
Select Keys
1-15
Key
Function
EVS Message Key 1
Select message slot to record to
EVS Message Key 3
Start and stop recording from Aux Audio Input
EVS Message Key 8
Erase user message 1-15
Select Keys 1-15
Message slot 1-15