Before You Begin Installation
3-10
1. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
2. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is calculated
by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK-DUCT.
3. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when
determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
5. Use next size battery with capacity greater than required.
6. Total does not include isolator devices or accessory bases.
3.7.3
Current Draw Worksheet for SD SLC Devices
Use to determine current requirements during alarm/battery standby operation when SD SLC devices are
installed. You can install up to 127 SD devices per loop.
5
Table 3-3: Current Draw Worksheet for SD SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery)
1
Standby: 190 mA
190 mA
Alarm: 250 mA
250 mA
Addressable SLC Devices
SD500-AIM
Standby/Alarm: .55 mA
1
mA
mA
SD500-MIM
mA
mA
SD500-PS
mA
mA
SD500-ARM
mA
mA
SD505-HEAT
mA
mA
SD505-PHOTO
mA
mA
SD500-ANM
Aux. Pwr
Standby: 8 mA
mA
Alarm: 60 mA
mA
SLC
Standby/Alarm: .55 mA
mA
mA
SD500-SDM
SLC
Standby/Alarm: .55 mA
mA
Aux. Pwr
Standby: 20 mA
mA
Alarm: 106 mA
mA
SLC Accessory Bases
SD505-6RB
Standby/Alram: .082 mA
mA
mA
SD505-6SB
Aux. Pwr
Standby: 1 mA
mA
Alarm: 32 mA
mA
SLC
Standby/Alarm .082 mA
mA
mA
SD505-DUCTR
Aux. Pwr
Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC
Standby/Alarm: .5 mA
mA
mA
SD505-DTS-K
None, included with SD505-DUCTR worst case.
SD505-DUCT
None, included with detector current.
SLC Isolator Devices
SD500-LIM
(100 max/loop)
Standby/Alarm .092 mA
mA
mA
SD505-6IB
Accessories Modules
5815XL SLC Loop Expander
(63 max.)
Standby/Alarm: 55 mA
mA
mA
6860 Remote LCD Annunciator.
(16 max.)
Standby: 25 mA
mA
Alarm: 50 mA
mA
5860 Remote LCD Annunciator.
Standby: 20 mA
mA
Alarm: 25 mA
mA
6855 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
5824 Serial/Parallel Printer Interface
(4 max.)
Standby/Alarm: 45 mA
mA
mA