EtherNet/IP 6-7
© 2005 HMS Industrial Networks.
AB7607 User manual
Status Assembly
The status assembly is a collection of status and diagnostic information for the
Anybus-X DeviceNet interface. The information in the assembly is updated once
a second.
Note:
All information in the status assembly is stored in little endian format. The
least significant byte of multi-byte values is stored first.
Byte
Offset
Size
in Bytes
Data Type
Name
Description
0
4
UDINT
Scan Counter
The number of DeviceNet I/O scans
that have taken place since the Any-
bus-X was powered up.
4
8
64-bit Bit-
string
Faulted Node
Table
Indicates which DeviceNet slaves are
faulted.
Each bit represents the status of the
slave at the corresponding MAC ID.
12
8
64-bit Bit-
string
Auto Verify Error
Table
Indicates which DeviceNet slaves are
the incorrect device type.
Each bit represents the status of the
slave at the corresponding MAC ID.
20
8
64-bit Bit-
string
Idle Node Table
Indicates which DeviceNet slaves are
in Idle mode.
Each bit represents the status of the
slave at the corresponding MAC ID.
28
8
64-bit Bit-
string
Active Node
Table
Indicates which DeviceNet nodes are
configured in the Anybus-X’s scan
list. Each bit represents the status of
the slave at the corresponding MAC
ID.
Table 6-7 Status Assembly Format