6.2 Setup menu
All settings are preset except for the start level. The start level
depends on the inlet height and must be set during the start-up
phase. See section
. However, in case
adjustments are required, settings can be made via the setup
menu. To open the setup menu, mark the symbol
using the
button
and press the button
. Navigate through the menu by
means of the buttons
and
. Select the desired menu item by
pressing the button
. Enter values or select settings from a list
by means of the buttons
and
. Save the settings by pressing
the button
. See also fig. 15.
The following settings can be made:
• start level
• rated current
• stop delay
• start delay
• alarm delay
• sensor selection
• sensor calibration
• sensor offset
• time for maintenance
• alarm reset (manually or automatically)
• reset to factory settings.
Fig. 15
Menu structure for setup menu
*) These submenus are only needed when changing sensor
type. The sensors for Multilift MOG and MDG are already
calibrated. For more information, see service instructions.
T
M
05
18
08
38
11
*)
L_01 Start Level [mm]
Setup menu
180
250
315
3.8
I_02 Rated current [A]
T_01 Stop delay [sec.]
T_02 Start delay [sec.]
2
0
T_03 Alarm delay [sec.]
5
S00, S01
S_01 Sensor selection
C_01 Calibration
C_02 Offset
490
Manual
Automatic
0, 3, 6, 12
EXIT
EXIT Back to main menu
G_01 Reset to factory settings
A_01 Reset alarm
M_01 Maintenance interval [month]
Summary of Contents for LC 221 Series
Page 1: ...Multilift MOG MDG Installation and operating instructions GRUNDFOS INSTRUCTIONS...
Page 2: ...2...
Page 46: ...BG 46 6 2 1 LC 221 6 2 LC 221 10 LC 221 TM05 1806 3811...
Page 49: ...BG 49 7 LC 221 7 1 LC 221 14 14 LC 221 TM05 1861 3811 1234 AUTO 7 3 7 2...
Page 50: ...BG 50 1 1 1 2 2 2...
Page 189: ...GR 189 5 2 1 LC 221 5 2 LC 221 10 LC 221 TM05 1806 3811...
Page 192: ...GR 192 6 LC 221 6 1 LC 221 14 14 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2...
Page 193: ...GR 193 1 1 1 2 2 2...
Page 332: ...KZ 332 5 2 1 LC 221 i 5 2 LC 221 i 10 LC 221 TM05 1806 3811...
Page 335: ...KZ 335 6 LC 221 6 1 LC 221 14 14 LC 221 TM05 1861 3811 1234 6 3 6 2...
Page 336: ...KZ 336 1 1 1 2 2 2...
Page 340: ...KZ 340 30 17 F015 1 1 F016 1 1 F017 2 2 F018 2 2 TM05 3455 0412...
Page 349: ...KZ 349 11 LC 221 Fault 1 a 5 2 LC 221 b 6 LC 221 c d F018 e f F005 F006 10 3 Grundfos g...
Page 474: ...UA 474 5 2 1 LC 221 5 2 LC 221 10 LC 221 TM05 1806 3811...
Page 477: ...UA 477 6 LC 221 6 1 LC 221 14 14 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2 Setup...
Page 478: ...UA 478 1 1 1 2 2 2...
Page 561: ...RU 561 7 2 1 LC 221 7 2 LC 221 10 LC 221 TM05 1806 3811...
Page 564: ...RU 564 8 LC 221 8 1 LC 221 14 14 LC 221 TM05 1861 3811 1234 8 3 8 2...
Page 565: ...RU 565 1 1 1 2 2 2...
Page 574: ...RU 574 10 2 LC 221 LC 221 6 26 10 3 IP65 1 5 CEE LC 221 TM05 1940 4011 LC 221...
Page 791: ...CN 791 5 2 1 LC 221 5 2 LC 221 4 10 LC 221 TM05 1806 3811...
Page 794: ...CN 794 6 LC 221 6 1 LC 221 14 14 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2...
Page 795: ...CN 795 1 1 1 2 2 2...
Page 799: ...CN 799 Man Auto ON OFF AUTO OFF ON OFF AUTO OFF 30 17 TM05 3455 0412...
Page 812: ...Appendix 812 Appendix 1 Fig A Dimensional sketch MOG TM05 0672 1011...
Page 813: ...Appendix 813 Fig B Dimensional sketch MDG TM05 0443 1011...
Page 814: ...814...
Page 815: ...815...
Page 816: ...816...