Page 1: ...l in the following manner to the product DANGER Immediate hazards which will result in yi CAUTION severe personal injury or death WARNING Hazards or unsafe practices which Signal Words on Product Labe...

Page 2: ...ight without modification to the drain pans or casing The drain pans remain in the same positions in the casing no matter which direction the air moves A CAUTION PRODUCT DAMAGE HAZARD Failure to follo...

Page 3: ...ion on a combustible floor Sub Base accessory must be installed between coil and floor Refer to Product Specification literature for accessory part number NOTE When coil is installed with a Heat Pump...

Page 4: ...service or water damage will occur NOTE For downflow electric furnace the secondary overflow drain connection must be installed to prevent possibility of water dripping onto live electrical components...

Page 5: ...e 6 Condensate Wires Condensate Management Wire both sides WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead of the waste line...

Page 6: ...TXV and nearby tubing with a heat sinking material such as a wet cloth 4 Fit refrigerant lines into coil stubs Wrap a heat sinking material such as a wet cloth behind braze joints NOTE See outdoor un...

Page 7: ...ton Check Static Pressure Drop and CFM Across Coil The amount of air CFM is related to a pressure drop To determine the CFM measure the pressure drop using an inclined manometer sometimes called draft...

Page 8: ...1 0 251 1600 0 320 0 336 800 0 101 0 106 4tons 7799 0 358 0 376 30F 900 0 121 0 129 1800 0 398 0 418 2 tons 1000 0 143 0 154 1400 0 192 0 196 1100 0 168 0 181 48 1500 0 219 0 225 1000 0 188 0 202 1600...

Page 9: ...gned to detect HFC refrigerant R 410A as with other HFC refrigerants is only compatible with POE oils POE coils absorb moisture rapidly Do not expose oil to atmosphere POE coils may cause damage to ce...