Problem
Problem
Problem
Cause
Cause
Cause
Solution
Solution
Solution
The wiring is incorrect.
Check the Modbus wiring between the Supervisor
Module and the fiber to serial converter.
• A = GND
• B = Data B(+) – Blue/White
• C = Data A(-) – White/Blue
Fiber ports are
backwards.
Verify the fiber port setup.
See
Modbus (RS-485) Wiring, page 34
.
• RX from ADCM Port 1 is connected to Fiber to Serial
Converter TX.
• TX from ADCM Port 2 is connected to Fiber to serial
Converter RX.
The fiber cable is set up
incorrectly.
Verify the fiber cable setup. See
Tank Control Modules to the Supervisor Box, page 38
The parameters are set
up incorrectly.
Check all parameters for your version (Lenze
SMVector or Allen Bradley PowerFlex 4M). See
Digital Input Configuration, page 28
The Variable
Frequency Drive/
Inverter (B) cannot
communicate with
the electric agitator.
The wiring is set up
incorrectly.
Verify the wiring. See
Drive/Inverter to the Supervisor Module, page 36
.
Node communication is
not enabled.
Turn on node communication.
See
Turn on Node Communication, page 67
.
The Radar Level Sensor
is not connected to the
correct port.
Verify that the Radar Level Sensor (M, T) is connected to
the correct port. See
Connect a Radar Level Sensor to a
Pump Control Module or Tank Control Module, page 27
.
The Radar Level
Sensor (M, T) will not
power on.
The power is not turned
on.
Make sure the box is enabled to turn on power in the
setup screens. See
Connect a Radar Level Sensor to a
Pump Control Module or Tank Control Module, page 27
.
The IP settings are
incorrect.
Verify that the IP address settings for Port 2 are correct.
See
Network Setup and Configuration, page 92
.
The Touchscreen
Box (J) cannot
communicate with
the Supervisor Box
(A).
The Ethernet cables are
plugged into the wrong
port.
Verify that the Ethernet connection between the
Supervisor Box and the Touchscreen Box. See
the Supervisor Box to the Touchscreen Box, page 41
132
3A4030C