4 Working with the master
4 Working with the master
The master allows the control and steering of all connected components.
It is protected from unauthorized access by a password: 137.
The available functions depend on the current configuration. A sample configuration is
described here.
4.1 Commissioning
The Hycleen Master starts automatically as soon as the voltage supply is switched on. A notice
then appears informing you that some settings first have to be performed. In this phase, all
valves supplied correctly with power flash blue and green alternately and can communicate
with the master.
The master first records and numbers the connected components. It groups each valve, sensor
etc. into the relevant function groups. The numbering starts at the left line and is then continued
at the right line, see also
.
The adjustment path of the valve plug for all valves of type LegioTherm 2T is also checked in
order to adjust the exact position of the valve plug.
It is not possible to enter any data during all these initialization processes. The indicator lights of
the valves light up yellow and the master checks the firmware version of each component. If an
update is necessary, this is performed automatically by the master and a message is displayed,
too.
Afterwards, the recorded components are displayed.