4 Working with the master
Process sequence for hot water (area = hot)
At the set
start-up time
the first valve regulates its flow to the set
temperature
, in the
shown example to 57 °C.
Then the second valve regulates its flow, followed by the other valves, and finally the pro-
cess is repeated until all valves reach the set
temperature
or the 4 hours have passed.
If the
temperature lower limit
(here: 50 °C) is fallen below, an error message appears
and an entry is made in the error log.
If the
temperature upper limit
(here: 90 °C) is exceeded, an error message appears
and an entry is made in the error protocol. These two limits must be defined mean-
ingfully, since they form the basis for an evaluation of the
.
If the checkmark at
Thermal disinfection (TD)
is set, the parameters shown below it
are displayed and active. Thermal disinfection process see
Process sequence for cold water (area = cold)
At the set
start-up time
the first valve regulates its flow to the set
temperature
, in the
shown example to 15 °C.
Then the second valve regulates its flow, followed by the other valves, and finally the pro-
cess is repeated until the 4 hours have passed.
If the
temperature lower limit
(here: 2 °C) is fallen below, an error message appears
and an entry is made in the error log.
If the
temperature upper limit
(here: 25 °C) is exceeded, an error message appears
and an entry is made in the error protocol. These two limits must be defined mean-
ingfully, since they form the basis for an evaluation of the
.
Thermal disinfection (TD)
is not necessary for cold water.
29
Summary of Contents for Hycleen Automation System
Page 1: ...GF Piping Systems Hycleen Automation System User Guide Version 2 0...
Page 2: ...ii...
Page 4: ...5 2 Error messages 54 6 Compliance 6 1 FCC 55 6 2 ISED 56 7 CE Declaration iv...
Page 6: ...6...
Page 52: ......
Page 57: ......