4 Working with the master
Process sequence for cold water (area = cold)
If the cold water becomes warmer than the
temperature
(here: 25 °C), then the process
starts and opens the valve. The resulting cold water circulation lowers the temperature.
T behavior cold water If the
temperature
is fallen below again, the valve closes again
(leakage rate).
If the
temperature lower limit
(here: 2 °C) is fallen below, an error message appears
and an entry is made in the error log.
If the
temperature upper limit
(here: 27 °C) is exceeded, an error message appears
and an entry is made in the error protocol.
Results and error messages are recorded in the protocol.
Thermal disinfection (TD)
is not necessary for cold water.