2 System Overview
2.2 Operating principle
The hot water and cold water circulations contain valves of the types
LegioTherm K
and
LegioTherm 2T
. The latter serves
(circulation system).
Both circulations can be
. The rinse water runs into a drain.
The LegioTherm valves are equipped with a temperature sensor.
All valves are connected with the
master
via power supply and communication cables serially
(i.e. not radial!), which also supplies them with power. The master controls the opening angle
of the valves according to its programming, taking into account the connected sensors and cre-
ates log data in the form of protocols.
After the valves are installed according to their operating instructions, they only must be
con-
nected
to
Hycleen Automation power supply and communication cables
. The power supplied
by the master via these connection cables. For cable lengths of more than 300 m and
additional
Hycleen Automation Powerbox
is required. Via its 2 cable connections, a master
with 2 power boxes can supply and control up to 1,000 m cable length.