4 Working with the master
In the case of weekly execution, e.g. Mondays and Wednesdays every week, set the
desired weekday, in the example here
on weekday
Monday and Wednesday:
Under
every x weeks
, set whether execution should take place weekly (x = 1, default
settings) or less frequently (x > 1).
If
run off monitoring
is installed, see
, it can be activated via
the checkmark. Under
level sensor
you can determine whether actuation of the signal
of the float switch closes
all
flush valves in the system (default setting and
recom-
mendation
), only the valve (
internally
), to which the sensor is connected, or a manually
selected flush valve – only such a valve is selectable.
4.4.7 Protocols
Select frequency (1) of the protocols and recording rate (2) of the measured values.
Activate selection with checkmark (4) or discard with x (3).