3 Installation
3.3 Installing other components
Extending the connecting cable
Use the
connector
(6) for connecting two connecting cables in series.
Installing the Powerbox
In the case of cable lengths longer than 300 m, switch a
powerbox
between two con-
necting cables. This way, the cable length can be extended by another 200 m to 500 m
maximum.
Connect the plug of the first connecting cable to one of the M12 plugs (9) of the power-
box and fasten with a knurled screw.
Connect the plug of the second connecting cable to the second M12 plug (9) of the
powerbox and fasten with a knurled screw.
Only insert the cold-device plug of the power cable into the connection (8) to begin the
startup of the system once all components have been correctly cabled.
The LED (7) of the powerbox lights up green.
14