5 Troubleshooting
5.2 Error messages
10004: Power supply < 28V
Measures:
Check: cable length in line with the specification.
10005: TCP/IP error
Measures:
Check the cable connections.
Check the IP addresses.
10013: PT 1000 Temperature sensor defective
Measures:
Replace PT 1000 temperature sensor.
10014: PT 1000 temperature sensor not connected
Measures:
Check the cable connection of the temperature sensor.
Connect the temperature sensor according to the installation instructions.
10016: Controller communication error
Measures:
Check the cable connection.
Connect the temperature sensor according to the installation instructions.
10029: Actuator defective
Measures:
Check the cable connection of the temperature sensor.
Check the actuator and controller.
Connect the actuator according to the installation instructions.
Replace the controller
10030: Valve blocked
Measures:
Check the actuator and controller.
Uninstall and check the valve top section and controller.
10050: Level sensor was actuated (NOK)
Measures:
Identify the concerned flushing valve and check the associated process.