Installation
Vacuum operation
GE Information
08- 2016
L31- 881EN04
2/6
Simple vacuum operation
Process
The table below gives the steps of the simple vacuum operation :
Step
Action
Comment/Diagram
1
Start the vacuum pump to evacu-
ate the pole to a value
1 mbar
(100 Pa)
.
KEEP THE PUMP RUNNING
FOR AT LEAST 1 HOUR AT
THIS VALUE.
2
Close the tap (1) of the vacuum
pump.
Open
Closed
1
3
Stop the vacuum pump.
4
Disconnect the vacuum pump
tube (2).
2
5
Fit the filling tool (4) - HAND
TIGHT.
4
END OF PROCEDURE