GE Multilin
F60 Feeder Protection System
2-1
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2
2 PRODUCT DESCRIPTION 2.1INTRODUCTION
2.1.1 OVERVIEW
The F60 Feeder Protection System is a microprocessor based relay designed for feeder protection.
Overvoltage and undervoltage protection, overfrequency and underfrequency protection, breaker failure protection, direc-
tional current supervision, fault diagnostics, RTU, and programmable logic functions are provided. This relay also provides
phase, neutral, ground and negative sequence, instantaneous and time overcurrent protection. The time overcurrent func-
tion provides multiple curve shapes or FlexCurves™ for optimum co-ordination. Automatic reclosing, synchrocheck, and
line fault locator features are also provided. When equipped with a type 8Z CT/VT module, an element for detecting high
impedance faults is provided.
Voltage, current, and power metering is built into the relay as a standard feature. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include a sequence of records capable of storing 1024 time-tagged events. The internal clock used for
time-tagging can be synchronized with an IRIG-B signal or via the SNTP protocol over the Ethernet port. This precise time
stamping allows the sequence of events to be determined throughout the system. Events can also be programmed (via
FlexLogic™ equations) to trigger oscillography data capture which may be set to record the measured parameters before
and after the event for viewing on a personal computer (PC). These tools significantly reduce troubleshooting time and sim-
plify report generation in the event of a system fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual val-
ues. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering staff. All serial ports use the Modbus
®
RTU protocol. The RS485 ports may be connected to system computers
with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules
include a 10Base-F Ethernet interface which can be used to provide fast, reliable communications in noisy environments.
Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus
®
/
TCP, and TFTP protocols, and allows access to the relay via any standard web browser (F60 web pages). The IEC 60870-
5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
The F60 IEDs use flash memory technology which allows field upgrading as new features are added. The following single
line diagram illustrates the relay functionality using ANSI (American National Standards Institute) device numbers.
Table 2–1: ANSI DEVICE NUMBERS AND FUNCTIONS
DEVICE
NUMBER
FUNCTION
DEVICE
NUMBER
FUNCTION
25 (2)
Synchrocheck
51P
Phase time overcurrent
27P (2)
Phase undervoltage
51_2
Negative-sequence time overcurrent
27X
Auxiliary undervoltage
52
AC circuit breaker
32
Sensitive directional power
59N
Neutral overvoltage
32N
Wattmetric zero-sequence directional
59P
Phase overvoltage
50BF/50NBF
Breaker failure
59X
Auxiliary overvoltage
50DD
Disturbance detector
59_2
Negative-sequence overvoltage
50G
Ground instantaneous overcurrent
67N
Neutral directional overcurrent
50N
Neutral instantaneous overcurrent
67P
Phase directional
50P
Phase instantaneous overcurrent
67_2
Negative-sequence directional overcurrent
50_2
Negative-sequence instantaneous overcurrent
79
Automatic recloser
51G
Ground time overcurrent
81O
Overfrequency
51N
Neutral time overcurrent
81U
Underfrequency
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...