2-12
F60 Feeder Protection System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
±2.0% of reading
Range:
±0 to 1
×
10
6
Mvarh
Parameters:
three-phase only
Update rate:
50 ms
CURRENT HARMONICS
Harmonics:
2nd to 25th harmonic: per phase, dis-
played as a % of f
1
(
fundamental fre-
quency phasor)
THD: per phase, displayed as a % of f
1
Accuracy:
HARMONICS:
1. f
1
> 0.4pu: (0.20% + 0.035% / harmonic) of
reading or 0.15% of 100%, whichever is
greater
2. f
1
< 0.4pu: as above plus %error of f
1
THD:
1. f
1
> 0.4pu: (0.25% + 0.035% / harmonic) of
reading or 0.20% of 100%, whichever is
greater
2. f
1
< 0.4pu: as above plus %error of f
1
VOLTAGE HARMONICS
Harmonics:
2nd to 25th harmonic: per phase, dis-
played as a % of f
1
(
fundamental fre-
quency phasor)
THD: per phase, displayed as a % of f
1
Accuracy:
HARMONICS:
1. f
1
> 0.4pu: (0.20% + 0.035% / harmonic) of
reading or 0.15% of 100%, whichever is
greater
2. f
1
< 0.4pu: as above plus %error of f
1
THD:
1. f
1
> 0.4pu: (0.25% + 0.035% / harmonic) of
reading or 0.20% of 100%, whichever is
greater
2. f
1
< 0.4pu: as above plus %error of f
1
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu:
±0.001 Hz (when voltage signal is used
for frequency measurement)
I = 0.1 to 0.25 pu:
±0.05 Hz
I > 0.25 pu:
±0.001 Hz (when current signal is used
for frequency measurement)
DEMAND
Measurements:
Phases A, B, and C present and maxi-
mum measured currents
3-Phase Power (P, Q, and S) present
and maximum measured currents
Accuracy:
±2.0%
2.2.5 INPUTS
AC CURRENT
CT rated primary:
1 to 50000 A
CT rated secondary:
1 A or 5 A by connection
Nominal frequency:
20 to 65 Hz
Relay burden:
< 0.2 VA at rated secondary
Conversion range:
Standard CT:
0.02 to 46
×
CT rating RMS symmetrical
Sensitive Ground CT module:
0.002 to 4.6
×
CT rating RMS symmetrical
HI-Z CT module:
0.002 to 4.6
×
CT rating RMS symmetri-
cal
Current withstand:
20 ms at 250 times rated
1 sec. at 100 times rated
continuous at 3 times rated
AC VOLTAGE
VT rated secondary:
50.0 to 240.0 V
VT ratio:
1.00 to 24000.00
Nominal frequency:
20 to 65 Hz
Relay burden:
< 0.25 VA at 120 V
Conversion range:
1 to 275 V
Voltage withstand:
continuous at 260 V to neutral
1 min./hr at 420 V to neutral
CONTACT INPUTS
Dry contacts:
1000
Ω
maximum
Wet contacts:
300 V DC maximum
Selectable thresholds:
17 V, 33 V, 84 V, 166 V
Tolerance:
±10%
Contacts per common return: 4
Recognition time:
< 1 ms
Debounce time:
0.0 to 16.0 ms in steps of 0.5
Continuous current draw:3 mA (when energized)
CONTACT INPUTS WITH AUTO-BURNISHING
Dry contacts:
1000
Ω
maximum
Wet contacts:
300 V DC maximum
Selectable thresholds:
17 V, 33 V, 84 V, 166 V
Tolerance:
±10%
Contacts per common return: 2
Recognition time:
< 1 ms
Debounce time:
0.0 to 16.0 ms in steps of 0.5
Continuous current draw:3 mA (when energized)
Auto-burnish impulse current: 50 to 70 mA
Duration of auto-burnish impulse: 25 to 50 ms
DCMA INPUTS
Current input (mA DC):
0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10,
0 to 20, 4 to 20 (programmable)
Input impedance:
379
Ω
±10%
Conversion range:
–1 to + 20 mA DC
Accuracy:
±0.2% of full scale
Type:
Passive
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...