6-14
F60 Feeder Protection System
GE Multilin
6.3 METERING
6 ACTUAL VALUES
6
DELTA-CONNECTED INSTRUMENT TRANSFORMERS:
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
*
The power system voltages are phase-referenced – for simplicity – to
VAG
and
VAB
, respectively. This, however, is a
relative matter. It is important to remember that the F60 displays are always referenced as specified under
SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
POWER SYSTEM
ÖØ
FREQUENCY AND PHASE REFERENCE
.
The example above is illustrated in the following figure.
Figure 6–3: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS
•
ABC phase rotation:
•
ACB phase rotation:
Table 6–1: SYMMETRICAL COMPONENTS CALCULATION EXAMPLE
SYSTEM VOLTAGES, SEC. V *
VT
CONN.
RELAY INPUTS, SEC. V
SYMM. COMP, SEC. V
V
AG
V
BG
V
CG
V
AB
V
BC
V
CA
F5AC
F6AC
F7AC
V
0
V
1
V
2
13.9
∠
0°
76.2
∠
–125°
79.7
∠
–250°
84.9
∠
–313°
138.3
∠
–97°
85.4
∠
–241°
WYE
13.9
∠
0°
76.2
∠
–125°
79.7
∠
–250°
19.5
∠
–192°
56.5
∠
–7°
23.3
∠
–187°
UNKNOWN (only
V
1 and
V
2
can be determined)
84.9
∠
0°
138.3
∠
–144°
85.4
∠
–288°
DELTA
84.9
∠
0°
138.3
∠
–144°
85.4
∠
–288°
N/A
56.5
∠
–54°
23.3
∠
–234°
V_0
N/A
=
V_1
1
30
–
°
∠
3 3
--------------------
V
AB
aV
BC
a
2
V
CA
+
+
(
)
=
V_2
1 30
°
∠
3 3
-----------------
V
AB
a
2
V
BC
aV
CA
+
+
(
)
=
V_0
N/A
=
V_1
1 30
°
∠
3 3
-----------------
V
AB
a
2
V
BC
aV
CA
+
+
(
)
=
V_2
1
30
–
°
∠
3 3
--------------------
V
AB
aV
BC
a
2
V
CA
+
+
(
)
=
827844A1.CDR
A
B
C
W
YE VTs
1
0
2
A
B
C
DELTA VTs
1
2
SYST
E
M VOLTAG
E
S
SYMM
E
TR
I
CAL
COMPO
NEN
TS
UR phase angle
reference
UR phase angle
reference
UR phase angle
reference
UR phase angle
reference
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...