2-8
F60 Feeder Protection System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
NEUTRAL DIRECTIONAL OVERCURRENT
Directionality:
Co-existing forward and reverse
Polarizing:
Voltage, Current, Dual
Polarizing voltage:
V_0 or VX
Polarizing current:
IG
Operating current:
I_0
Level sensing:
3
×
(|I_0| –
K
×
|I_1|), IG
Restraint,
K
:
0.000 to 0.500 in steps of 0.001
Characteristic angle:
–90 to 90° in steps of 1
Limit angle:
40 to 90° in steps of 1, independent for
forward and reverse
Angle accuracy:
±2°
Offset impedance:
0.00 to 250.00
Ω
in steps of 0.01
Pickup level:
0.002 to 30.000 pu in steps of 0.01
Dropout level:
97 to 98%
Operation time:
< 16 ms at 3
×
pickup at 60 Hz
NEGATIVE SEQUENCE DIRECTIONAL OC
Directionality:
Co-existing forward and reverse
Polarizing:
Voltage
Polarizing voltage:
V_2
Operating current:
I_2
Level sensing:
Zero-sequence:|I_0| –
K
×
|I_1|
Negative-sequence:|I_2| –
K
×
|I_1|
Restraint,
K
:
0.000 to 0.500 in steps of 0.001
Characteristic angle:
0 to 90° in steps of 1
Limit angle:
40 to 90° in steps of 1, independent for
forward and reverse
Angle accuracy:
±2°
Offset impedance:
0.00 to 250.00
Ω
in steps of 0.01
Pickup level:
0.015 to 30.000 pu in steps of 0.01
Dropout level:
97 to 98%
Operation time:
< 16 ms at 3
×
pickup at 60 Hz
WATTMETRIC ZERO-SEQUENCE DIRECTIONAL
Measured power:
zero-sequence
Number of elements:
2
Characteristic angle:
0 to 360° in steps of 1
Minimum power:
0.001 to 1.200 pu in steps of 0.001
Pickup level accuracy:
±1% or ±0.0025 pu, whichever is greater
Hysteresis:
3% or 0.001 pu, whichever is greater
Pickup delay:
definite time (0 to 600.00 s in steps of
0.01), inverse time, or FlexCurve
Inverse time multiplier:
0.01 to 2.00 s in steps of 0.01
Time accuracy:
±3% or ±20 ms, whichever is greater
Operate time:
<30 ms at 60 Hz
SENSITIVE DIRECTIONAL POWER
Measured power:
3-phase, true RMS
Number of stages:
2
Characteristic angle:
0 to 359° in steps of 1
Calibration angle:
0.00 to 0.95° in steps of 0.05
Minimum power:
–1.200 to 1.200 pu in steps of 0.001
Pickup level accuracy:
±1% or ±0.001 pu, whichever is greater
Hysteresis:
2% or 0.001 pu, whichever is greater
Pickup delay:
0 to 600.00 s in steps of 0.01
Time accuracy:
±3% or ±4 ms, whichever is greater
Operate time:
50 ms
PHASE UNDERVOLTAGE
Voltage:
Phasor only
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Curve shapes:
GE IAV Inverse;
Definite Time (0.1s base curve)
Curve multiplier:
Time dial = 0.00 to 600.00 in steps of
0.01
Timing accuracy:
Operate at < 0.90
×
pickup
±3.5% of operate time or ±4 ms (which-
ever is greater)
AUXILIARY UNDERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Curve shapes:
GE IAV Inverse, Definite Time
Curve multiplier:
Time Dial = 0 to 600.00 in steps of 0.01
Timing accuracy:
±3% of operate time or ±4 ms
(whichever is greater)
PHASE OVERVOLTAGE
Voltage:
Phasor only
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 in steps of 0.01 s
Operate time:
<
30 ms at 1.10
×
pickup at 60 Hz
Timing accuracy:
±3% or ±4 ms (whichever is greater)
NEUTRAL OVERVOLTAGE
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0.00 to 600.00 s in steps of 0.01 (definite
time) or user-defined curve
Reset delay:
0.00 to 600.00 s in steps of 0.01
Timing accuracy:
±3% or ±20 ms (whichever is greater)
Operate time:
<
30 ms at 1.10
×
pickup at 60 Hz
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...