GE Multilin
F60 Feeder Protection System
B-37
APPENDIX B
B.4 MEMORY MAPPING
B
7F38
Reserved (8 items)
0 to 65535
---
1
F001
0
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F61
Auxiliary Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F62
Auxiliary Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
700
7F63
Auxiliary Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7F64
Auxiliary Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7F65
Auxiliary Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7F66
Auxiliary Undervoltage 1 Block
0 to 65535
---
1
F300
0
7F67
Auxiliary Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F68
Auxiliary Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F69
Reserved (7 items)
0 to 65535
---
1
F001
0
7F70
...Repeated for Auxiliary Undervoltage 2
7F80
...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000
Tracking Frequency
---
Hz
---
F001
0
EGD Fast Production Status (Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83E1
EGD Fast Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83E3
EGD Fast Producer Exchange 1 Size
0 to 65535
---
1
F001
0
EGD Slow Production Status (Read Only) (2 modules)
83F0
EGD Slow Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
83F1
EGD Slow Producer Exchange 1 Configuration Time
0 to 4294967295
---
---
F003
0
83F3
EGD Slow Producer Exchange 1 Size
0 to 65535
---
1
F001
0
83F4
...Repeated for module number 2
EGD Fast Production (Read/Write Setting)
8400
EGD Fast Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8401
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8403
EGD Fast Producer Exchange 1 Data Rate
50 to 1000
ms
50
F001
1000
8404
EGD Fast Producer Exchange 1 Data Item 1 (20 items)
0 to 65535
---
1
F001
0
8418
Reserved (80 items)
---
---
---
F001
0
EGD Slow Production (Read/Write Setting) (2 modules)
8500
EGD Slow Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
8501
EGD Fast Producer Exchange 1 Destination
0 to 4294967295
---
1
F003
0
8503
EGD Slow Producer Exchange 1 Data Rate
500 to 1000
ms
50
F001
1000
8504
EGD Slow Producer Exchange 1 Data Item 1 (50 items)
0 to 65535
---
1
F001
0
8536
Reserved (50 items)
---
---
---
F001
0
8568
...Repeated for EGD Exchange 2
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 65535
---
1
F300
0
8606
Breaker Failure 1 Block
0 to 65535
---
1
F300
0
8607
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
8608
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
8609
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860A
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860B
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...