5-74
F60 Feeder Protection System
GE Multilin
5.3 SYSTEM SETUP
5 SETTINGS
5
5.3.5 DISCONNECT SWITCHES
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
SWITCHES
Ö
SWITCH 1(8)
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the F60.
•
SWITCH 1 FUNCTION:
This setting enables and disables the operation of the disconnect switch element.
•
SWITCH 1 NAME:
Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
•
SWITCH 1 MODE:
This setting selects “3-pole” mode, where all disconnect switch poles are operated simultaneously,
or “1-pole” mode where all disconnect switch poles are operated either independently or simultaneously.
SWITCH 1
SWITCH 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
SWITCH 1 NAME:
SW 1
Range: up to 6 alphanumeric characters
MESSAGE
SWITCH 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
SWITCH 1 OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 BLK OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 BLK CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
SWTCH 1
Φ
A/3P CLSD:
Off
Range: FlexLogic™ operand
MESSAGE
SWTCH 1
Φ
A/3P OPND:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
B CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
B OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
C CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1
Φ
C OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
SWITCH 1 Toperate:
0.070 s
Range: 0.000 to 2.000 s in steps of 0.001
MESSAGE
SWITCH 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
SWITCH 1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...