AN-55 Terminal 42 Output Filter
Option:
Function:
The following readout parameters from selection in
parameter AN-50 Terminal 42 Output
have a filter
selected when
parameter AN-55 Terminal 42 Output
is on:
Selection
0–20 mA
4–20 mA
Motor current (0–I
max
)
[103]
[133]
Torque limit (0–T
lim
)
[104]
[134]
Rated torque (0–T
nom
)
[105]
[135]
Power (0–P
nom
)
[106]
[136]
Speed (0–Speed
max
)
[107]
[137]
Table 3.11 Readout Parameters
[0]
*
Off
Filter off.
[1]
On
Filter on.
3.7.8 AN-6# Analog Output 2 OPCGPIO
General Purpose I/O
Analog outputs are current outputs: 0/4–20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
AN-60 Terminal X30/8 Output
Same options and functions as
AN-61 Terminal X30/8 Min. Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scales the minimum output of the selected analog
signal on terminal X30/8. Scale the minimum value
as a percentage of the maximum signal value, that
is 0 mA (or 0 Hz) is required at 25% of the
maximum output value and 25% is programmed.
The value can never exceed the corresponding
parameter AN-62 Terminal X30/8 Max.
if the value is below 100%.
This parameter is active when General Purpose I/O
OPCGPIO General Purpose I/O is mounted in the
frequency converter.
AN-62 Terminal X30/8 Max. Scale
Range:
Function:
100
%
*
[0 -
200 %
]
Scales the maximum output of the selected
analog signal on terminal X30/8. Scale the value
to the required maximum value of the current
signal output. Scale the output to give a lower
current than 20 mA at full scale, or 20 mA at an
output below 100% of the maximum signal value.
If 20 mA is the required output current at a value
between 0–100% of the full-scale output,
program the percentage value in the parameter,
AN-62 Terminal X30/8 Max. Scale
Range:
Function:
that is 50%=20 mA. If a current 4–20 mA is
required at maximum output (100%), calculate
the percentage value as follows:
20
mA
/
desired
maximum
current
× 100 %
i
.
e
. 10
mA
:
20
mA
10
mA
× 100 % = 200 %
AN-63 Terminal X30/8 Output Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Contains the value to apply to the output
terminal when it is configured as bus-
controlled.
AN-64 Terminal X30/8 Output Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Contains the value to apply to the output
terminal, when it is configured as bus-
controlled timeout and timeout is detected.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
75