3.5 P-## Motor Data
3.5.1 P-0# Motor Data
P-02 Motor Power [HP]
Range:
Function:
4.00
hp
*
[0.09 -
3000.00
hp]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the nominal motor power in hp
according to the motor nameplate data. The
default value corresponds to the nominal
rated output of the unit.
Depending on the selections made in
parameter K-03 Regional Settings
, either
parameter P-07 Motor Power [kW]
or
parameter P-02 Motor Power [HP]
is made
invisible.
P-03 Motor Current
Range:
Function:
7.20 A
*
[0.10 -
10000.00 A]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the nominal motor current value
from the motor nameplate data. The
data is used for calculating motor
torque, motor thermal protection, and so
on.
P-04 Auto Tune
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
The Auto Tune function optimises dynamic
motor performance by automatically optimising
the advanced motor parameters
(
parameter P-30 Stator Resistance (Rs)
to
parameter P-35 Main Reactance (Xh)
) at motor
standstill.
[0]
*
Off
No function.
[1]
Full Auto
Tune
Performs Auto Tune of the stator resistance R
S
,
the rotor resistance R
r
, the stator leakage
reactance X
1
, the rotor leakage reactance X
2
and the main reactance X
h
.
[2]
Reduced
Auto Tune
Performs a reduced Auto Tune of the stator
resistance R
s
in the system only. Select this
option if an LC filter is used between the
frequency converter and the motor.
Activate the Auto Tune function by pressing [Hand ] after
selecting
[1] Enable complete AMA
or
[2] Enable reduced
AMA
. After a normal sequence, the display reads:
Press [OK]
to finish Auto Tune
. After pressing [OK], the frequency
converter is ready for operation.
NOTICE
•
For the best results of the frequency converter,
run Auto Tune on a cold motor.
•
Auto Tune cannot be performed while the
motor is running.
NOTICE
Avoid generating external torque during Auto Tune.
NOTICE
If 1 of the settings in parameter group
P-## Motor Data
is changed,
parameter P-30 Stator Resistance (Rs)
return to default settings.
NOTICE
Only run complete Auto Tune without filter, and only run
reduced Auto Tune with filter.
P-06 Base Speed
Range:
Function:
1420
RPM
*
[100 -
60000 RPM]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the nominal motor speed value
from the motor nameplate data. The
data is used for calculating automatic
motor compensations.
P-07 Motor Power [kW]
Range:
Function:
4.00
kW
*
[0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data. The
default value corresponds to the nominal
rated output of the unit.
Depending on the selections made in
parameter K-03 Regional Settings
, either
parameter P-07 Motor Power [kW]
parameter P-02 Motor Power [HP]
is made
invisible.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
57