XC-50 Ext. 3 Ref./Feedback Unit
Option:
Function:
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft3/s
[126] ft3/min
[127] ft3/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
XC-51 Ext. 3 Minimum Reference
Range:
Function:
0 ExtPID3Unit
*
[-999999.999 - par.
XC-52 ExtPID3Unit]
See
for
details.
XC-52 Ext. 3 Maximum Reference
Range:
Function:
100
ExtPID3Unit
*
[par. XC-51 -
999999.999
ExtPID3Unit]
See
for
details.
XC-53 Ext. 3 Reference Source
Option:
Function:
See
parameter XC-13 Ext. 1 Reference
for details.
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital Potentiometer
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
XC-54 Ext. 3 Feedback Source
Option:
Function:
See
parameter XC-14 Ext. 1 Feedback
for details.
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog Input X30/11
[8]
Analog Input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100] Bus Feedback 1
[101] Bus Feedback 2
[102] Bus feedback 3
XC-55 Ext. 3 Setpoint
Range:
Function:
0 ExtPID3Unit
*
[par. XC-51 - par.
XC-52 ExtPID3Unit]
See
for details.
XC-57 Ext. 3 Reference [Unit]
Range:
Function:
0 ExtPID3Unit
*
[-999999.999 -
999999.999
ExtPID3Unit]
See
for details.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D