3.26 B-##
Braking
Functions
3.26.1 B-0# DC brakes
Parameter group for configuring the DC brake and DC hold
functions.
B-00 DC Hold Current
Range:
Function:
50
%
*
[0 -
160 %
]
NOTICE
Parameter B-00 DC Hold Current
has no
effect when
[1] PM, non-salient SPM
.
NOTICE
The maximum value depends on the rated
motor current.
Avoid 100% current for too long. It may
damage the motor.
Enter a value for holding current as a percentage
of the rated motor current I
M,N
set in
. 100% DC hold
current corresponds to I
M,N
.
This parameter holds the motor (holding torque) or
preheats the motor.
This parameter is active if
[1] DC hold/Motor
Preheat
is selected in
B-01 DC Brake Current
Range:
Function:
50
%
*
[0 -
1000 %
]
NOTICE
The maximum value depends on the rated
motor current. Avoid 100% current for too
long. It may damage the motor.
Enter a value for current as a percentage of the
rated motor current I
M,N
, see
. 100% DC brake current corresponds to
I
M,N
.
DC brake current is applied on a stop command,
when the speed is lower than the limit set in:
•
Parameter B-03 DC Brake Cut In Speed
.
•
Parameter B-04 DC Brake Cut In Speed
, when the DC brake inverse function
is active, or via the serial communication
port.
The braking current is active during the time
parameter B-02 DC Braking Time
.
B-02 DC Braking Time
Range:
Function:
10 s
*
[0 - 60 s] Set the duration of the DC brake current set in
parameter B-01 DC Brake Current
, once
activated.
B-03 DC Brake Cut In Speed [RPM]
Range:
Function:
0 RPM
*
[0 - 0
RPM]
Set the DC brake cut-in speed for activation
of the DC braking current set in
parameter B-01 DC Brake Current
, upon a
stop command.
When
parameter P-20 Motor Construction
is
set to
[1] PM non-salient SPM
, this value is
limited to 0 RPM (OFF).
B-04 DC Brake Cut In Speed [Hz]
Range:
Function:
0.0 Hz
*
[0 - 0.0
Hz]
This parameter is for setting the DC brake
cut-in speed at which the DC braking
current (
parameter B-01 DC Brake Current
) is
to be active in connection with a stop
command.
B-06 Parking Current
Range:
Function:
50
%
*
[0 -
1000 %]
NOTICE
Parameter B-06 Parking Current
and
: Only active
if
[1] PM, non salient SPM
is selected in
parameter P-20 Motor Construction
.
Set current as percentage of rated motor
current,
. Active in
. The
parking current is active during the time period
set in
B-07 Parking Time
Range:
Function:
3 s
*
[0.1 - 60
s]
Set the duration of the parking current time set
in
parameter B-06 Parking Current
. Active in
connection with
.
NOTICE
is only active
when
[1] PM, non-salient SPM
is selected
in
parameter P-20 Motor Construction
.
Parameter Description
194
03/2016 All rights reserved.
DET-620D