3.25 LC-## Logic Controller
3.25.1 LC-## Logic Controller
Logic Controller (LC) is a sequence of user-defined actions
(see
parameter LC-52 Logic Controller Action
[x]) executed by
the LC when the associated user-defined event (see
parameter LC-51 Logic Controller Event
[x]) is evaluated as
TRUE by the LC. Events and actions are each numbered
and linked together in pairs. This means that when [0]
event is fulfilled (attains the value TRUE), [0] action is
executed. After this, the conditions of [1] event are
evaluated and if evaluated TRUE, [1] action is executed and
so on. Only 1 event is evaluated at any time. If an event is
evaluated as FALSE, nothing happens (in the LC) during the
current scan interval and no other events are evaluated.
This means that when the LC starts, it evaluates [0] event
(and only [0] event) at each scan interval. Only when [0]
event is evaluated TRUE, the LC executes [0] action and
starts evaluating [1] event. It is possible to program from 1
to 20 events and actions.
When the last event/action has been executed, the
sequence starts over again from [0] event/[0] action.
shows an example with 3 events/actions
Illustration 3.74 Example with 3 Events/Actions
Starting and stopping the LC
Start and stop the LC by selecting
[1] On
or
[0] Off
in
parameter LC-00 Logic Controller Mode
. The LC always starts
in state 0 (where it evaluates
[0] event
). The LC starts when
) is
evaluated as TRUE (provided that
[1] On
is selected in
parameter LC-00 Logic Controller Mode
). The LC stops when
the stop event (
) is TRUE.
Parameter LC-03 Reset Logic Controller
resets all LC
parameters and starts programming from scratch.
3.25.2 LC-0# LC Settings
Use the LC settings to activate, deactivate, and reset the
Logic Controller.
LC-00 Logic Controller Mode
Option:
Function:
[0]
*
Off
Disables the logic controller.
[1]
On
Enables the logic controller.
LC-01 Start Event
Option:
Function:
Select the boolean (TRUE or FALSE)
input to activate Logic Controller.
[0]
False
Enters the fixed value of FALSE in the
logic rule.
[1]
True
Enters the fixed value TRUE in the logic
rule.
[2]
Running
See parameter group
E-2#
for further
description.
[3]
In range
See parameter group
E-2#
for further
description.
[4]
On reference
See parameter group
E-2#
for further
description.
[5]
Torque limit
See parameter group
E-2#
for further
description.
[6]
Current Limit
See parameter group
E-2#
for further
description.
[7]
Out of current
range
See parameter group
E-2#
for further
description.
[8]
Below I low
See parameter group
E-2#
for further
description.
[9]
Above I high
See parameter group
E-2#
for further
description.
[10]
Out of speed
range
[11]
Below speed low See parameter group
E-2#
for further
description.
[12]
Above speed
high
See parameter group
E-2#
for further
description.
[13]
Out of feedb.
range
[14]
Below feedb. low
[15]
Above feedb.
high
[16]
Thermal warning
See parameter group
E-2#
for further
description.
[17]
Line voltage out
of range
See parameter group
E-2#
for further
description.
[18]
Reversing
See parameter group
E-2#
for further
description.
[19]
Warning
See parameter group
E-2#
for further
description.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
183
3
3