O-50 Coasting Select
Option:
Function:
Select the trigger for the coasting function.
[0]
Digital
input
A digital input triggers the coasting function.
[1]
Bus
A serial communication port or the network
option module triggers the coasting function.
[2]
Logic AND
The network/serial communication port and a
digital input trigger the coasting function.
[3]
*
Logic OR
The network/serial communication port or a
digital input trigger the coasting function.
O-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTICE
When
parameter P-20 Motor Construction
is
set to
[1] PM non-salient SPM
, only
selection
[0] Digital input
is available.
[0]
Digital
input
Activates a DC Brake command via a digital
input.
[1]
Bus
Activates a DC Brake command via the serial
communication port or network option module.
[2]
Logic
AND
Activates a DC Brake command via the network/
serial communication port, and also via 1 of the
digital inputs.
[3]
*
Logic OR Activates a DC Brake command via the network/
serial communication port, or via 1 of the digital
inputs.
O-53 Start Select
Option:
Function:
Select the trigger for the start function.
[0]
Digital
input
A digital input triggers the start function.
[1]
Bus
A serial communication port or the network
option module triggers the start function.
[2]
Logic AND
The network/serial communication port and a
digital input trigger the start function.
[3]
*
Logic OR
The network/serial communication port or a
digital input trigger the start function.
O-54 Reversing Select
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
O-54 Reversing Select
Option:
Function:
Select control of the drive reverse function via
the terminals (digital input) and/or via the
fieldbus.
[0]
*
Digital
input
Activates reverse command via a digital input.
[1]
Bus
Activates reverse command via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates reverse command via the fieldbus/serial
communication port, AND via 1 of the digital
inputs.
[3]
Logic
OR
Activates reverse command via the fieldbus/serial
communication port OR via 1 of the digital
inputs.
O-55 Set-up Select
Option:
Function:
Select the trigger for the set-up selection.
[0]
Digital
input
A digital input triggers the set-up selection.
[1]
Bus
A serial communication port or the network
option module triggers the set-up selection.
[2]
Logic AND
The network/serial communication port and a
digital input trigger the set-up selection.
[3]
*
Logic OR
The network/serial communication port or a
digital input trigger the set-up selection.
O-56 Preset Reference Select
Option:
Function:
Select the trigger for the preset reference
selection.
[0]
Digital
input
A digital input triggers the preset reference
selection.
[1]
Bus
A serial communication port or the network
option module triggers the preset reference
selection.
[2]
Logic AND
The network/serial communication port and a
digital input trigger the preset reference
selection.
[3]
*
Logic OR
The network/serial communication port or a
digital input trigger the preset reference
selection.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.