3.10.4 AO-3# Analog Input X42/5
AO-30 Terminal X42/5 Low Voltage
Range:
Function:
0.07 V
*
[0 - par.
AN-31 V]
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
parameter AO-34 Term. X42/5 Low Ref./
.
AO-31 Terminal X42/5 High Voltage
Range:
Function:
10 V
*
[par. AN-30
- 10 V]
Enter the high voltage value. This analog
input scaling value should correspond to
the high reference/feedback value set in
parameter AO-35 Term. X42/5 High Ref./
AO-34 Term. X42/5 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999]
Enter the analog input scaling value that
corresponds to the low voltage value set
in
parameter AO-30 Terminal X42/5 Low
AO-35 Term. X42/5 High Ref./Feedb. Value
Range:
Function:
100
*
[-999999.999 -
999999.999]
Enter the analog input scaling value
that corresponds to the high voltage
value set in
AO-36 Term. X42/5 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor runs.
This is a first-order digital low-pass filter
time constant for suppressing noise in
terminal X42/5. A high time constant
value improves dampening, but also
increases the time delay through the
filter.
AO-37 Term. X42/5 Live Zero
Option:
Function:
Enable or disable the live zero monitoring.
[0]
Disabled
[1]
*
Enabled
3.10.5 AO-4# Analog Out X42/7
AO-40 Terminal X42/7 Output
Option:
Function:
Set the function of terminal X42/7 as an
analog current output.
[0]
*
No operation
[100] Output
frequency
0–100 Hz, (0–10 V).
[101] Reference
Minimum reference–maximum reference,
(0–10 V).
[102] Feedback
-200% to +200% of
parameter F-53 Maximum Reference
, (0–10
V).
[103] Motor Current
0–inverter maximum current
(
parameter DR-37 Drive Max. Current
), (0–
10 V).
[104] Torque rel to
limit
0–torque limit (
), (0–10 V).
[105] Torq relate to
rated
0–motor rated torque, (0–10 V).
[106] Power
0–motor rated power, (0–10 V).
[107] Speed
0–speed high limit (
parameter F-15 Motor Speed High Limit
), (0–10 V).
[113] Ext. Closed
Loop 1
0–100%, (0–10 V).
[114] Ext. Closed
Loop 2
0–100%, (0–10 V).
[115] Ext. Closed
Loop 3
0–100%, (0–10 V).
[139] Bus ctrl.
0–100%, (0–10 V).
[141] Bus ctrl t.o.
0–100%, (0–10 V).
AO-41 Terminal X42/7 Min. Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scale the minimum output of the selected analog
signal at terminal X42/7, as a percentage of the
maximum signal level, example, if 0 V (or 0 Hz) is
desired at 25% of the maximum output value,
program 25%. Scaling values up to 100% can
never be higher than the corresponding setting in
parameter AO-42 Terminal X42/7 Max. Scale
.
.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
91
3
3