The input will go low whenever the Logic
Action [33]
Set dig. out. A low
is executed.
[82]
Logic
Controller
digital output
C
See
parameter LC-52 Logic Controller Action
.
The input will go high whenever the Logic
Action [40]
Set dig. out. A high
is executed.
The input will go low whenever the Logic
Action [34]
Set dig. out. A low
is executed.
[83]
Logic
Controller
digital output
D
See
parameter LC-52 Logic Controller Action
.
The input will go high whenever the Logic
Action [41]
Set dig. out. A
high is executed.
The input will go low whenever the Logic
Action [35]
Set dig. out. A low
is executed.
[84]
Logic
Controller
digital output
E
See
parameter LC-52 Logic Controller Action
.
The input will go high whenever the Logic
Action [42]
Set dig. out. A high
is executed.
The input will go low whenever the Logic
Action [36]
Set dig. out. A low
is executed.
[85]
Logic
Controller
digital output
F
See
parameter LC-52 Logic Controller Action
.
The input will go high whenever the Logic
Action [43]
Set dig. out. A high
is executed.
The input will go low whenever the Logic
Action [37]
Set dig. out. A low
is executed.
[160] No alarm
Output is high when no alarm is present.
[161] Running
reverse
Output is high when the frequency
converter is running counter clockwise (the
logical product of the status bits ‘running’
AND ‘reverse’).
[165] Local ref
active
Output is high when
parameter F-02 Operation Method
= [2]
Local or when
parameter F-02 Operation
Method
= [0]
Linked to hand auto
at the
same time as the keypad is in Hand mode.
[166] Remote ref
active
Output is high when
parameter F-02 Operation Method
= Remote
[1] or
Linked to hand/auto
[0] while the
keypad is in [Auto] mode.
[167] Start
command act.
Output is high when there is an active
Start command (i.e. via digital input bus
connection or [Hand] or [Auto]), and no
Stop or Start command is active.
[168] Hand mode
Output is high when the frequency
converter is in Hand mode (as indicated by
the LED light above [Hand]).
[169] Auto mode
Output is high when the frequency
converter is in Auto mode (as indicated by
the LED light above [on]).
[180] Clock Fault
The clock function has been reset to
default (2000-01-01) because of a power
failure.
[181] Prev.
Maintenance
One or more of the Preventive
Maintenance Events programmed in
parameter T-10 Maintenance Item
has
passed the time for the specified action in
parameter T-11 Maintenance Action
[190] No-Flow
A No-Flow situation or Minimum Speed
situation has been detected if enabled in
parameter AP-21 Low Power Detection
and/or
[191] Dry Pump
A Dry Pump condition has been detected.
This function must be enabled in
parameter AP-26 Dry Pump Function
[192] End Of Curve
A pump running with max. speed for a
period of time without reaching the set
pressure has been detected. To enable this
function please see
[193] Sleep Mode
The frequency converter/system has
turned into sleep mode. See parameter
group AP-4#.
[194] Broken Belt
A Broken Belt condition has been
detected. This function must be enabled in
parameter AP-60 Broken Belt Function
[195] Bypass Valve
Control
The bypass valve control (Digital / Relay
output in the frequency converter) is used
for compressor systems to unload the
compressor during start-up by using a
bypass valve. After the start command is
given the bypass valve will be open until
the frequency converter reaches
parameter F-18 Motor Speed Low Limit
) . After the limit has been reached
the bypass valve will be closed, allowing
the compressor to operate normally. This
procedure will not be activated again
before a new start is initiated and the
frequency converter speed is zero during
the receiving of start signal.
can be used
in order to delay the motor start. The
Bypass valve control principle:
Illustration 3.15
[196] Fire Mode
The frequency converter is operating in
Fire Mode. See parameter group FB-0#
Fire
Mode
.
[197] Fire Mode was
Act.
The frequency converter has been
operating in Fire Mode, but is now back in
normal operation.
[198] Drive Bypass
To be used as signal for activating an
external electromechanical bypass
switching the motor direct on line. See
FB-1#
Drive Bypass
.
[200] Full capacity
All pumps running and at full speed
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
47